NEW QUESTION 146
What are the main components of the natural cooling source system? (Multiple choice)

  • A. Natural cooling on the water side
  • B. Chilled water cooling scheme
  • C. Direct ventilation and natural cooling
  • D. Natural cooling by runner heat exchange

Answer: A,C,D

 

NEW QUESTION 147
When the single cell voltage in the battery pack reaches ( ), it means that the battery pack is already in a risky state. (Fill in the blank)

  • A. 1.67V

Answer: A

 

NEW QUESTION 148
The external maintenance bypass of the UPS system generally uses a circuit breaker with ( ) pole.

  • A. 0
  • B. 1
  • C. 2
  • D. 3

Answer: C

 

NEW QUESTION 149
How many temperature and humidity monitoring modules are required for each temperature control product?

  • A. 0
  • B. 1
  • C. 2
  • D. 3

Answer: D

 

NEW QUESTION 150
The row-level air conditioners (25kw and 42kw) of Huawei FusionModule2000 v3.0 have the refrigerant detection function.

  • A. True
  • B. False

Answer: A

 

NEW QUESTION 151
The device is connected to the ECC800 monitoring system through the smart ETH socket, using the () interface of the smart FTH socket.

  • A. RS485
  • B. POE
  • C. AI/DI
  • D. FE

Answer: B

 

NEW QUESTION 152
What are the functions provided by the Huawei surveillance system NETECO? (Multiple choice)

  • A. Support modular/cabinet-level view display
  • B. Provide 2D, 3D data center view display
  • C. Only provide view creation tools to facilitate and quickly configure views
  • D. Support system power distribution view display

Answer: A,B,C,D

 

NEW QUESTION 153
The operating temperature range of FusionModule800 is -40-45 degrees, and the operating temperature range of FusionModule500 is 0~45 degrees.

  • A. True
  • B. False

Answer: B

 

NEW QUESTION 154
The function of the back-feed protection card is that when the energy back-feed occurs in the main circuit or the bypass, the back-feed protection card sends a drive alarm signal, and the drive trip switch (configured by the customer) is disconnected, which plays the role of back-feed protection.

  • A. True
  • B. False

Answer: A

 

NEW QUESTION 155
The ECC800 does not support SMS notification of alarms and cannot realize remote maintenance.

  • A. True
  • B. False

Answer: B

 

NEW QUESTION 156
Regarding intelligent battery management in UPS5000-A, which of the following statements is correct? (Multiple choice)

  • A. Intelligent Floating Charge Conversion
  • B. The number of battery cells is adjustable
  • C. Support battery sleep
  • D. Support battery temperature compensation

Answer: A,B,C,D

 

NEW QUESTION 157
When the NetCol5000-A compressor runs for a long time with low superheat or no superheat, it is prone to "liquid shock" and damage.

  • A. True
  • B. False

Answer: A

 

NEW QUESTION 158
UPS5000-S-400K adopts () KVA power module.

  • A. 0
  • B. 1
  • C. 2
  • D. 3

Answer: D

 

NEW QUESTION 159
A single row of FusionModule2000 supports a maximum of ( ) cabinets. (Fill in the blank)

  • A. 24

Answer: A

 

NEW QUESTION 160
Which of the following fan control modes are supported by NetCo18000-C series room-level chilled water intelligent cooling products? (Multiple choice)

  • A. Return air control
  • B. Mixed air control
  • C. Pressure Control
  • D. Supply air control
  • E. Differential pressure control

Answer: A,B,C,D,E

 

NEW QUESTION 161
When calculating the battery capacity, the battery discharge capacity system at different backup time is the same.

  • A. True
  • B. False

Answer: B

 

NEW QUESTION 162
Which of the following descriptions of the iPower function of the intelligent micro-module of Fusionllodule2000 v3.0 are correct? (Multiple choice)

  • A. Intelligent rPDU can monitor the power consumption information of each socket
  • B. Power Distribution Link Visualization
  • C. With alarm convergence function (mains power failure scenario, alarm information collection)
  • D. Can monitor battery information

Answer: B,C,D

 

NEW QUESTION 163
What is the channel width of Huawei FusionModule2000?

  • A. 1200mm
  • B. 1300mm
  • C. 1000mm
  • D. 1100mm

Answer: A

 

NEW QUESTION 164
When the inspection, maintenance and repair of electrical installations are carried out in a non-stop work mode, warning signs or signs should be hung in the electrical installations and work area.

  • A. TRUE
  • B. FALSE

Answer: A

 

NEW QUESTION 165
If the NETCOL5000-A air-conditioning unit operates abnormally, you should check whether the compressor, fan, and pipe lights are fixed properly and whether there is any looseness.

  • A. True
  • B. False

Answer: A

 

NEW QUESTION 166
The refrigerant cylinder of Huawei air-cooled air conditioner does not need to be placed upside down on the electronic scale when charging refrigerant.

  • A. True
  • B. False

Answer: B

 

NEW QUESTION 167
After the start-up and debugging of the air conditioner, the indoor temperature is in a reasonable state, and the suction pressure is not lower than () can be regarded as reasonable.

  • A. 0.7MPA
  • B. 7MPA
  • C. 6MPA
  • D. 5MPA

Answer: A

 

NEW QUESTION 168
NETCOL9000-A100KW is a dual system, and the standard configuration is a single indoor unit connected to an outdoor unit.

  • A. True
  • B. False

Answer: B

 

NEW QUESTION 169
......